Online Arc Flash Calculator IEEE 1584 (2002 and 2018) | jCalc.NET (2024)

Calculate Arc Flash Boundary and Arc Flash Incident Energy with the Free Arc Flash Calculator. Supports IEEE 1584-2002, IEEE 1584-2018, and the Ralph Lee Method.

See Also

  • 5 Minimum Arc Flash Label Requirements NFPA 2018.
  • Cable sizing calculator AS/NZS3008
  • Maximum demand calculator AS/NZS3000

Parameters for the IEEE 1584 2018 Arc Flash Calculator

  • Standard: Select IEEE 1584-2018 or IEEE 1584-2002.
  • Unit of measure: Imperial (in) or Metric (mm). Note that Conductor Gap is always in metric.
  • Voltage (Vac): Enter an AC voltage between 208 V and 15,000 V.AC voltage levels outside of this range, and DC voltage levels, are not supported by the IEEE 1584-2018.
  • Fault current (kA): Three-phase bolted prospective fault current in kA.
  • Arcing time for Iarc (ms):
    • The fault clearing time for the calculated normal arching current.
    • Include the protection relay and circuit breaker clearing time.
    • Follow a three-step process to specify the arching time:.
    • Step 1: Leave the default time value, and click on Calculate.
    • Step 2: Use the calculated arcing current Iarc to determine the actual fault clearing time for your protection system,
    • Step 3: Click on Calculate again, to calculate the Incident Energy and Arc Flash Boundary.
    • Note that the time does not affect the magnitude of the acing current.
  • Arcing time for Iarc_min (ms):
    • The purpose of this is to calculate the Incident Energy and Arc Flash Boundary for a scenario where the fault clearing time may be longer due to a reduced arcing current.
    • This is the arcing time for the calculated reduced arcing current.
    • Follow the same steps as explained above for the arcing time for the normal arcing current.
  • Working distance (inch or mm): The working distance from the arc location. This field is pre-populated with typical distances from IEEE 1584 2018, which is based on the Equipment Type.
  • Equipment Type:
    • The Equipment Type is used to pre-populate the following distances and sizes with typical values from the IEEE 1584 2018:
      • Working Distance.
      • Enclosure Sizes (width, height, and depth).
      • Conductor Gap.
    • You can change these values after you have selected the equipment type.
    • The Equipment Type is not used in the calculations. Only the values are used.
  • Enclosure width, height and depth (inch or mm): You can change the typical enclosure (box) sizes here.These values are pre-populated with typical values from IEEE 1548 2018, based on the selected Equipment Type.
  • Electrode configuration: Choose from the following:
    • VCB: Vertical conductor (electrode) in a box.
    • VCBB: Vertical conductor (electrode) in a box terminated in an insulating barrier.
    • HCB: Horizontal conductor (electrode) in a box.
    • VOA: Vertical conductor (electrode) in open air.
    • HOA: Horizontal conductor (electrode) in open air.
  • Conductor gap (mm): The distance between the conductors (electrodes).This value is always in mm.It is pre-populated with typical values from IEEE 1548 2018, based on the selected Equipment Type.

Parameters for the IEEE 1584 2002 Arc Flash Calculator

  • Standard: Select IEEE 1584-2018 or IEEE 1584-2002.
  • Unit of measure: Imperial (in) or Metric (mm). Note that Conductor Gap is always in metric.
  • Voltage (Vac): Enter an AC voltage between 208 V and 15,000 V.AC voltage levels outside of this range, and DC voltage levels, are not supported by the IEEE 1584-2002.
  • Fault current (kA): Three-phase bolted prospective fault current in kA.
  • Arcing time for Iarc (ms):
    • The fault clearing time for the calculated normal arching current.
    • Include the protection relay and circuit breaker clearing time.
    • Follow a three-step process to specify the arching time:.
    • Step 1: Leave the default time value, and click on Calculate.
    • Step 2: Use the calculated arcing current Iarc to determine the actual fault clearing time for your protection system,
    • Step 3: Click on Calculate again, to calculate the Incident Energy and Arc Flash Boundary.
    • Note that the time does not affect the magnitude of the acing current.
  • Working distance (inch or mm): The working distance from the arc location. This field is pre-populated with typical distances from IEEE 1584 2018, which is based on the Equipment Type.
  • Equipment Type:
    • The Equipment Type is used to pre-populate the following distances and sizes with typical values from the IEEE 1584 2002:
      • Working Distance.
      • Conductor Gap.
    • You can change these values after you have selected the equipment type.
    • The Equipment Type is used in the calculations.
  • Grounding: The grounding type is used in calculations.
  • Conductor gap (mm): The distance between the conductors (electrodes).This value is always in mm.It is pre-populated with typical values from IEEE 1548 2018, based on the selected Equipment Type.

Ralph Lee Method

The calculator also supports the Ralph Lee Method,which is one of the proposed methods in theNFPA 70E standard.

PPE Categories in NFPA 70E 2018

There are two official Arc Flash Analysis (Study) methods defined by NFPA 70E:

  • Incident Energy Analysis Method
  • Arc Flash PPE Category Method

You can read more about it in What is an Arc Flash Study? Two Official Methods Described

This calculator is based on the Incident Energy Method.

According to NFPA 70E, PPE Categories should not be used when the Incident Energy Method is used.However, NFPA 70E allows site-specific PPE requirements on Arc Flash Labels, and in many cases, sites adopt the PEE Categories anyway.

For more information see 5 Minimum Arc Flash Label Requirements from NFPA 70E 2018

Therefore, I have included the mapping to Arc Flash Categories in the calculator.

The PPE in NFPA 70E is defined into 4 categories.

Table 1: NFPA 70E PPE Categories
CategoryMinimum arc rating of PPE
01.2 cal/cm2
14 cal/cm2
28 cal/cm2
325 cal/cm2
440 cal/cm2

Note that Category 0 is not listed in NFPA 70E.I have included it here when the incident energy is less than 1.2 cal/cm2.In other words, when the Arc Flash Boundary is less than the working distance.

Equipment types with typical distances and sizes for IEEE 1584 2018

Abbreviations used in Table 2 and Table 3:

GapConductor Gap (mm)
WDWorking distance (inch or mm)
HEnclosure height (inch or mm)
WEnclosure width (inch or mm)
DEnclosure depth (inch or mm)

Table 2: Equipment Types with Typical Imperial Distances and Measurements (IEEE 1584 2018)
Equipment typeGap mmWD inH inW inD in
15 kV Switchgear15236453030
15 kV MCC15236363636
5 kV Switchgear, Large10436363636
5 kV Switchgear, Small10436453030
5 kV MCC10436262626
LV Switchgear3224202020
LV MCCs and Panels, Shallow251814128
LV MCCs and Panels, Deep251814129
Cable Junction Box, Shallow131814128
Cable Junction Box, Deep131814129

Table 3: Equipment Types with Typical Metric Distances and Measurments (IEEE 1584 2018)
Equipment typeGap mmWD mmH mmW mmD mm
15 kV Switchgear1529141143762762
15 kV MCC152914914914914
5 kV Switchgear, Large104914914914914
5 kV Switchgear, Small1049141143762762
5 kV MCC104914660660660
LV Switchgear32610508508508
LV MCCs and Panels, Shallow25457355.6305203
LV MCCs and Panels, Deep25457355.6305229
Cable Junction Box, Shallow13457355.6305203
Cable Junction Box, Deep13457355.6305229

Equipment types with typical distances and sizes for IEEE 1584 2002

Table 4: Typical Conductor Gaps in IEEE 1584 2002
System voltageEquipment typeConductor gap
0.208-1 kVOpen air10-40 mm
Switchgear32 mm
MCCS and panels25 mm
Cables13 mm
>1-5 kVOpen air102 mm
Switchgear13-102 mm
Cables13 mm
>5-15 kVOpen air13-153 mm
Switchgear153 mm
Cables13 mm

Table 5: Typical working distances in IEEE 1584 2002
SystemWorking distance
15-kV switchgear910 mm
5-kV switchgear910 mm
Low-voltage switchgear610 mm
Low-voltage MCCs and panelboards455 mm
Cable455 mm

How to calculate the Arc Flash Boundary with IEEE 1584 2018?

The Arc Flash Boundary is calculated according to IEEE 1584 2018 as follows:

  1. Calculate the intermediate arching currents Iarc_600, Iarc_2700 and Iarc_14300 at 600V, 2700V and 14300V.
  2. Calculate the final arcing current Iarc at the specified open circuit operating voltage Voc.
  3. Calculate the enclosure size correction factor CF for the relevant electrode configuration and enclosure size.
  4. Calculate the intermediate arc flash boundaries AFB600, AFB2700 and AFB14300 at 600V, 2700V and 14300V.
  5. Calculate the final arc flash boundary AFB at the specified open circuit operating voltage Voc.

How to calculate the Arc Flash Incident Energy with IEEE 1584 2018?

The Arc Flash Incident Energy is calculated according to IEEE 1584 2018 as follows:

  1. Calculate the intermediate arching currents Iarc_600, Iarc_2700 and Iarc_14300 at 600V, 2700V and 14300V.
  2. Calculate the final arcing current Iarc at the specified open circuit operating voltage Voc.
  3. Calculate the enclosure size correction factor CF for the relevant electrode configuration and enclosure size.
  4. Calculate the intermediate arc flash boundaries E600, E2700 and E14300 at 600V, 2700V and 14300V.
  5. Calculate the final Incident Energy E at the specified open circuit operating voltage Voc.
Online Arc Flash Calculator IEEE 1584 (2002 and 2018) | jCalc.NET (2024)

References

Top Articles
Latest Posts
Article information

Author: Domingo Moore

Last Updated:

Views: 6550

Rating: 4.2 / 5 (53 voted)

Reviews: 92% of readers found this page helpful

Author information

Name: Domingo Moore

Birthday: 1997-05-20

Address: 6485 Kohler Route, Antonioton, VT 77375-0299

Phone: +3213869077934

Job: Sales Analyst

Hobby: Kayaking, Roller skating, Cabaret, Rugby, Homebrewing, Creative writing, amateur radio

Introduction: My name is Domingo Moore, I am a attractive, gorgeous, funny, jolly, spotless, nice, fantastic person who loves writing and wants to share my knowledge and understanding with you.